Investigation and control of a cluster of cases of Legionnaires disease in western Sydney

J. Brown*, K. Hort, R. Bouwman, A. Capon, N. Bansal, I. Goldthorpe, K. Chant, S. Vemulpad

*Corresponding author for this work

    Research output: Contribution to journalArticlepeer-review

    14 Citations (Scopus)

    Abstract

    Three cases of Legionella pneumophila infection were identified in Sydney's west in November 1998. Epidemiological investigations identified an association with one workplace. Environmental sampling revealed that the cooling towers in the workplace, and at 2 other premises within a 1 km radius of the workplace, were positive for L. pneumophila serogroup 1 (LP1) which was indistinguishable from clinical isolates of 2 of the cases on DNA fingerprinting. Our report highlights limitations of the current control program for Legionella in cooling towers, including the finding of unregistered cooling towers, cooling towers positive for LP1 despite satisfactory results on inspection, and cooling towers potentially linked to disease with counts of LP1 below the current protocol requirements for immediate decontamination.

    Original languageEnglish
    Pages (from-to)63-66
    Number of pages4
    JournalCommunicable diseases intelligence
    Volume25
    Issue number2
    Publication statusPublished - Apr 2001

    Fingerprint

    Dive into the research topics of 'Investigation and control of a cluster of cases of Legionnaires disease in western Sydney'. Together they form a unique fingerprint.

    Cite this